Illustration: an OS Power AI data center hall with liquid-cooled GPU racks

AI and GPU

GPU infrastructure from 100 kW to 5 MW

We design the hall for the platform the customer has chosen: air-cooled GPU servers, mixed halls and liquid-cooled supernode racks up to 140 kW. Power, cooling and storage are sized for the pulsed load of model training.

up to 140 kW

per rack with liquid cooling

manufacturer data

75-90%

of heat is removed by cold plates on accelerators

industry data

1 MW

site in 8-12 months from contract signing to acceptance

OS Power calculation

Reference designs

What hall your platform needs

Guideline for 1 MW of IT load. The exact scope is calculated for the server model and number of accelerators.

Rack classkW per rackRacks per 1 MWCoolingOS Power format
Air-cooled GPU servers10-2050-100air, aisle containmentmicro-module, container, prefabricated data center
Mixed hall20-4025-50air and rear-door heat exchangersmicro-module, prefabricated data center
High-density liquid-cooled racks40-8013-25 + networkdirect-to-chip liquid, CDUprefabricated data center
Supernode racks120-1427-9 + 4-6 networkdirect-to-chip liquid, supply at 30-45 °Cprefabricated data center, power blocks + hall
Next generationup to 600per designliquid, 800 V DCspace and busbars reserved in the design

Load pulses

Why an AI data center needs energy storage

Training clusters change their consumption by tens of percent within fractions of a second. These pulses wear out UPS batteries and disturb the grid. OS Power supercapacitors on the hall busbar absorb the pulses, LFP or NFPP storage carries the load until the gensets start and shaves peaks, and the gensets run less often.

Power supply

Future readiness

What we build into the design now

800 V DC

Space and busbars for DC-powered racks that accelerator manufacturers are preparing from 2027.

Supply up to 45 °C

The site circuit is designed for warm water for new platforms: more free cooling hours, no compressors.

Expansion

A second IT module, a second cooling plant and a second transformer are included in the site plan.

Slab without raised floor

Point rack loads up to 2 t, overhead cable trays.

OS Power does not supply, purchase or service computing equipment. Servers are supplied and imported by the customer or a licensed supplier in compliance with applicable export controls.