Generation

Genset model range

Diesel gensets 6-4,000 kVA at 50 and 60 Hz, data center units, 48 V DC gensets, containerized power modules and monitoring. Manufacturer data, 2025-2026.

Ratings

Prime and standby: how to read the rating

Power is stated per ISO 8528. The rating determines how many hours and at what load a unit can operate.

RatingConditionsPurpose
Primeunlimited hours, average load up to 70 %, 10 % overload for no more than 1 h in 12primary source
Standbygrid failure only, average load up to 80 %, less than 500 h per year, no overloadbackup
Data centerunlimited hours at variable loaddata center backup

Range

Series by engine

The same rating is available with different engines: we select by availability, lead time, service and customer requirements.

50 Hz, 1,500 rpm, 400/230 V

EngineSmallest model prime / standby, kVALargest model prime / standby, kVAConsumption at 100 % prime, l/h
Perkins8.5 / 9.52,250 / 2,5002.5-469
Cummins20 / 222,250 / 2,5005.7-450
MTU450 / 5003,300 / 3,600102-668
Mitsubishi9 / 102,500 / 2,7502.75-512
SDEC40 / 44500 / 55010.7-102
Yanmar5.5 / 655 / 601.7-13.9
Weichai23 / 253,000 / 3,3006.1-630
Yuchai20 / 223,250 / 3,5006.3-731

60 Hz, 1,800 rpm, 220/480 V

EngineSmallest model prime / standby, kVALargest model prime / standby, kVAConsumption at 100 % prime, l/h
Perkins10.5 / 11.51,715 / 1,8803.0-356
Cummins22 / 252,250 / 2,7507.1-485
MTU510 / 5603,500 / 4,075106-704
Mitsubishi12 / 132,275 / 2,5253.4-466
SDEC44 / 48450 / 50011.5-105
Yanmar6.5 / 7.569 / 752.0-16.6
Weichai27 / 303,750 / 4,1006.5-768
Yuchai22 / 242,500 / 2,7506.7-544

Typical points

Power, consumption and dimensions

ClassPrime / standby, kVAConsumption, l/hDimensions L×W×H, mmWeight, kg
100 kVA100 / 11021.81,660 × 900 × 1,3501,150
500 kVA500 / 560983,400 × 1,150 × 2,1503,850
1,000 kVA1,000 / 1,1002104,800 × 2,050 × 2,2507,200
2,000 kVA2,000 / 2,2504225,800 × 2,250 × 2,65012,500

Perkins engine series, 50 Hz, open design. For other engines and designs - see the datasheet.

Designs

Designs

Open
on a base frame with tank, for a generator hall
Enclosed
sound-attenuated, super-silent - from 55 dBA at 1 m at 75 % load
20 and 40 ft container
up to 4,000 kVA, including double-stacked
Trailer and skid
mobile units
Methanol
45-55 % lower CO2 and 60-80 % lower NOx compared with diesel

Standard scope

Standard scope of supply

  • Brushless Leroy-Somer or Stamford alternator, AREP and PMG options
  • Radiator for +40 °C with engine-driven fan
  • Anti-vibration mounts, base frame fuel tank, industrial silencer
  • Auto-start control panel with protections and graphic display
  • Starter and 12/24 V batteries, output circuit breaker
  • Testing of every unit at 0, 25, 50, 75, 100 and 110 % load

Data centers

Units with data center rating

For Tier III and IV data center backup, 50 Hz, 400/230 V.

EngineAlternatorData center rating, open, kWEnclosed, kW
Mitsubishi S16R2-PTAW2-ELeroy-Somer LSA 52.32,0001,992
MTU 20V4000G23FLeroy-Somer LSA 52.32,0001,992
MTU 20V4000G63FLeroy-Somer LSA 53.22,2002,200
MTU 20V4000G63LFLeroy-Somer LSA 53.22,4002,354

For data centers: modularity, integration with power modules, fuel supply control, industrial silencers; the noise calculation is performed for the specific site.

Data center backup power

Telecom

48 V DC gensets

For base stations and network nodes without a reliable grid.

Output
12-48 V DC
Power
5-27 kW
Alternator efficiency
over 90-95 %
Fuel savings
40-60 % through variable engine speed
Service
kit for 1,000 engine hours
Hybrid
solar, wind, LFP and NFPP storage

Gensets for base stations

Power modules

Containerized power modules

Genset, distribution, transformer and UPS in factory-built containers.

Power
up to 3,000 kVA per module
Scope
ring distribution, transformer, genset and grid incomers, UPS, feeders
Design
40 ft container, IP55, N+1 air conditioning, gas fire suppression
Layout
double-stacked containers: genset on top, distribution below
Fuel
double-wall day tank, PLC-controlled fuel supply

Monitoring

Monitoring system

Remote monitoring of gensets, storage and solar plants at distributed sites.

Fuel

level, abnormal drop, specific consumption, refuelling forecast

Genset

engine hours, filter clogging, alarms, remote start and stop

Storage

remaining autonomy, cycles, condition

Security

door sensors, electronic locks, video surveillance

Communication

RS232, RS485, CAN, Modbus, SNMP; 4G, Ethernet, fiber

Alerts

SMS, e-mail, Telegram; web interface and mobile app

Specifications are manufacturer data, 2025-2026. Availability of engine brands and lead times are confirmed in the commercial proposal.