Generation
Genset model range
Diesel gensets 6-4,000 kVA at 50 and 60 Hz, data center units, 48 V DC gensets, containerized power modules and monitoring. Manufacturer data, 2025-2026.
Ratings
Prime and standby: how to read the rating
Power is stated per ISO 8528. The rating determines how many hours and at what load a unit can operate.
| Rating | Conditions | Purpose |
|---|---|---|
| Prime | unlimited hours, average load up to 70 %, 10 % overload for no more than 1 h in 12 | primary source |
| Standby | grid failure only, average load up to 80 %, less than 500 h per year, no overload | backup |
| Data center | unlimited hours at variable load | data center backup |
Range
Series by engine
The same rating is available with different engines: we select by availability, lead time, service and customer requirements.
50 Hz, 1,500 rpm, 400/230 V
| Engine | Smallest model prime / standby, kVA | Largest model prime / standby, kVA | Consumption at 100 % prime, l/h |
|---|---|---|---|
| Perkins | 8.5 / 9.5 | 2,250 / 2,500 | 2.5-469 |
| Cummins | 20 / 22 | 2,250 / 2,500 | 5.7-450 |
| MTU | 450 / 500 | 3,300 / 3,600 | 102-668 |
| Mitsubishi | 9 / 10 | 2,500 / 2,750 | 2.75-512 |
| SDEC | 40 / 44 | 500 / 550 | 10.7-102 |
| Yanmar | 5.5 / 6 | 55 / 60 | 1.7-13.9 |
| Weichai | 23 / 25 | 3,000 / 3,300 | 6.1-630 |
| Yuchai | 20 / 22 | 3,250 / 3,500 | 6.3-731 |
60 Hz, 1,800 rpm, 220/480 V
| Engine | Smallest model prime / standby, kVA | Largest model prime / standby, kVA | Consumption at 100 % prime, l/h |
|---|---|---|---|
| Perkins | 10.5 / 11.5 | 1,715 / 1,880 | 3.0-356 |
| Cummins | 22 / 25 | 2,250 / 2,750 | 7.1-485 |
| MTU | 510 / 560 | 3,500 / 4,075 | 106-704 |
| Mitsubishi | 12 / 13 | 2,275 / 2,525 | 3.4-466 |
| SDEC | 44 / 48 | 450 / 500 | 11.5-105 |
| Yanmar | 6.5 / 7.5 | 69 / 75 | 2.0-16.6 |
| Weichai | 27 / 30 | 3,750 / 4,100 | 6.5-768 |
| Yuchai | 22 / 24 | 2,500 / 2,750 | 6.7-544 |
Typical points
Power, consumption and dimensions
| Class | Prime / standby, kVA | Consumption, l/h | Dimensions L×W×H, mm | Weight, kg |
|---|---|---|---|---|
| 100 kVA | 100 / 110 | 21.8 | 1,660 × 900 × 1,350 | 1,150 |
| 500 kVA | 500 / 560 | 98 | 3,400 × 1,150 × 2,150 | 3,850 |
| 1,000 kVA | 1,000 / 1,100 | 210 | 4,800 × 2,050 × 2,250 | 7,200 |
| 2,000 kVA | 2,000 / 2,250 | 422 | 5,800 × 2,250 × 2,650 | 12,500 |
Perkins engine series, 50 Hz, open design. For other engines and designs - see the datasheet.
Designs
Designs
- Open
- on a base frame with tank, for a generator hall
- Enclosed
- sound-attenuated, super-silent - from 55 dBA at 1 m at 75 % load
- 20 and 40 ft container
- up to 4,000 kVA, including double-stacked
- Trailer and skid
- mobile units
- Methanol
- 45-55 % lower CO2 and 60-80 % lower NOx compared with diesel
Standard scope
Standard scope of supply
- Brushless Leroy-Somer or Stamford alternator, AREP and PMG options
- Radiator for +40 °C with engine-driven fan
- Anti-vibration mounts, base frame fuel tank, industrial silencer
- Auto-start control panel with protections and graphic display
- Starter and 12/24 V batteries, output circuit breaker
- Testing of every unit at 0, 25, 50, 75, 100 and 110 % load
Data centers
Units with data center rating
For Tier III and IV data center backup, 50 Hz, 400/230 V.
| Engine | Alternator | Data center rating, open, kW | Enclosed, kW |
|---|---|---|---|
| Mitsubishi S16R2-PTAW2-E | Leroy-Somer LSA 52.3 | 2,000 | 1,992 |
| MTU 20V4000G23F | Leroy-Somer LSA 52.3 | 2,000 | 1,992 |
| MTU 20V4000G63F | Leroy-Somer LSA 53.2 | 2,200 | 2,200 |
| MTU 20V4000G63LF | Leroy-Somer LSA 53.2 | 2,400 | 2,354 |
For data centers: modularity, integration with power modules, fuel supply control, industrial silencers; the noise calculation is performed for the specific site.
Telecom
48 V DC gensets
For base stations and network nodes without a reliable grid.
- Output
- 12-48 V DC
- Power
- 5-27 kW
- Alternator efficiency
- over 90-95 %
- Fuel savings
- 40-60 % through variable engine speed
- Service
- kit for 1,000 engine hours
- Hybrid
- solar, wind, LFP and NFPP storage
Power modules
Containerized power modules
Genset, distribution, transformer and UPS in factory-built containers.
- Power
- up to 3,000 kVA per module
- Scope
- ring distribution, transformer, genset and grid incomers, UPS, feeders
- Design
- 40 ft container, IP55, N+1 air conditioning, gas fire suppression
- Layout
- double-stacked containers: genset on top, distribution below
- Fuel
- double-wall day tank, PLC-controlled fuel supply
Monitoring
Monitoring system
Remote monitoring of gensets, storage and solar plants at distributed sites.
Fuel
level, abnormal drop, specific consumption, refuelling forecast
Genset
engine hours, filter clogging, alarms, remote start and stop
Storage
remaining autonomy, cycles, condition
Security
door sensors, electronic locks, video surveillance
Communication
RS232, RS485, CAN, Modbus, SNMP; 4G, Ethernet, fiber
Alerts
SMS, e-mail, Telegram; web interface and mobile app
Specifications are manufacturer data, 2025-2026. Availability of engine brands and lead times are confirmed in the commercial proposal.
Products for this application
Full catalog
OSP-DGDiesel and gas gensets6-4,000 kVA
OSP-DG-DC4848 V generator5-27 kW
OSP-DG-PTUContainerized power blockup to 3,000 kVA
OSP-CI-NA-115L115 kWh sodium cabinet115 kWh
OSP-CT-NA-23962.4 MWh sodium container2.4 MWh
OSP-DC-PWRPower distribution module6-35 kV
OSP-PD-ATSAutomatic transfer switches (ATS)
OSP-TL-NA-48100Sodium module 48 V / 100 Ah-40 °C Request
Tell us about your site
Load and load profile, operating mode (backup or primary source), climate, grid availability, noise and fuel requirements. We will reply with a configuration, lead time and proposal.