Genset selector

Diesel genset LRYC1500

1,500 kVA standby and 1,375 kVA prime, 50 Hz, 400/230 V. Yuchai YC12VTD1830-D30 engine, Energis EG-1400-4 alternator, ISO 8528 class G3.

Diesel genset LRYC1500

All models / 50 Hz / LRYC1500

Standby1,500 kVA1,200 kW
Prime1,375 kVA1,100 kW
Fuel at 100 %305 L/hStandby 337 L/h
Specific fuel0.277L/kWh
Canopy weight16,900* kg12,192 × 2,438 × 2,896
Enclosure40 ft containerISO 8528 G3 · 400/230 V

Some values of this model are being confirmed with the manufacturer: container weight.

Ratings by voltage

Voltage, VStandby, kVAStandby, kWPrime, kVAPrime, kWCurrent, A
380/2201,5001,2001,3751,1002,279
400/2301,5001,2001,3751,1002,165
415/2401,5001,2001,3751,1002,086

Ratings per ISO 8528 at PF 0.8.

Fuel consumption

Datasheet values at 50, 75 and 100 % of prime and in standby duty.

0100200300 05001,000 kW L/h 158228305337
LoadPower, kWFuel, L/hL/kWh
50 %5501580.287
75 %8252280.276
100 %1,1003050.277
Standby1,2003370.281

Engine

Make
Yuchai
Model
YC12VTD1830-D30
Cylinders
12 V
Bore × stroke, mm
152 / 180
Aspiration
turbocharged and aftercooled
Compression ratio
14:1
Displacement, L
39.2
Speed, rpm
1,500
Governor
ECU
Engine prime power, kW
1,220
Engine maximum power, kW
1,342
Oil capacity, L
210
Starter, V
24

Alternator

Make
Energis
Model
EG-1400-4
Protection
IP21
Insulation class
H
Efficiency at 100 %, PF 0.8, %
94.9
Excitation
auxiliary winding
Voltage regulator
KR440
Voltage regulation
± 1 %

Dimensions and weight

VersionLength, mmWidth, mmHeight, mmWeight, kgTank, L
Open on base frame5,0002,2002,5008,650-
Canopy (40 ft container)12,192*2,438*2,896*16,900*-*

Specifications are manufacturer datasheet data, edition 08.2025; power factor 0.8; fuel consumption for diesel with a density of 0.85 kg/L. Model availability and lead time are confirmed in the commercial offer. Values marked * are being confirmed with the manufacturer.

Scope of supply and control

  • Set-mounted radiator with engine-driven fan, cooling system rated for +40 °C ambient
  • Anti-vibration mounts between engine, alternator and base frame
  • Base frame fuel tank (up to and including 825 kVA), oil and coolant drains with valves
  • Protective guards for fan and rotating parts
  • Exhaust bellows and industrial silencer
  • 12 or 24 V starter motor and battery
  • 3-pole output circuit breaker
  • Factory test of every set at 0, 25, 50, 75, 100 and 110 % load
  • Compliance with ISO 8528, ISO 3046, IEC 60034, BS 5000; manufacturing to ISO 9001 and ISO 14001; CE certificate

Control and protection

  • Standard controller with protections: high coolant temperature, low oil pressure, overspeed, start failure, over and under frequency and voltage, overload, overcurrent, emergency stop
  • Measurements: voltage, current, frequency, power factor, kW, kWh, kVA, running hours, number of starts
  • Options: automatic mains failure, fuel level, RS485 and Modbus RTU, Modbus TCP/IP, SNMP, extension modules
  • Alternative controllers: ComAp, DeepSea, Woodward, Smartgen
  • Parallel operation between sets and with the grid

Request

Tell us about your site

Load and load profile, operating mode (backup or primary source), climate, grid availability, noise and fuel requirements. We will reply with a configuration, lead time and proposal.