Genset selector

Diesel genset LRYC24X

24 kVA standby and 22 kVA prime, 60 Hz, 220/127 V. Yuchai YC4V35-D21 engine, Energis EG-20-4 alternator, ISO 8528 class G2.

Diesel genset LRYC24X

All models / 60 Hz / LRYC24X

Standby24 kVA20 kW
Prime22 kVA17.6 kW
Fuel at 100 %6.7 L/hStandby 7.6 L/h
Specific fuel0.381L/kWh
Canopy weight760 kg2,000 × 920 × 1,200
Enclosuresoundproof canopyISO 8528 G2 · 220/127 V

Ratings by voltage

Voltage, VStandby, kVAStandby, kWPrime, kVAPrime, kWCurrent, A
220/12724202217.662
440/25424202217.633
480/27724202217.630

Ratings per ISO 8528 at PF 0.8.

Fuel consumption

Datasheet values at 50, 75 and 100 % of prime and in standby duty.

0358 01020 kW L/h 3.75.26.77.6
LoadPower, kWFuel, L/hL/kWh
50 %8.83.70.42
75 %13.25.20.394
100 %17.66.70.381
Standby207.60.38

Engine

Make
Yuchai
Model
YC4V35-D21
Cylinders
4 in line
Bore × stroke, mm
89 / 100
Aspiration
naturally aspirated
Compression ratio
19:1
Displacement, L
2.5
Speed, rpm
1,800
Governor
electronic
Engine prime power, kW
25
Engine maximum power, kW
28
Oil capacity, L
7
Starter, V
12

Alternator

Make
Energis
Model
EG-20-4
Protection
IP21
Insulation class
H
Efficiency at 100 %, PF 0.8, %
83.2
Excitation
auxiliary winding
Voltage regulator
KRS440B
Voltage regulation
± 1 %

Dimensions and weight

VersionLength, mmWidth, mmHeight, mmWeight, kgTank, L
Open on base frame1,6507601,05058075
Canopy (soundproof canopy)2,0009201,20076075

Specifications are manufacturer datasheet data, edition 08.2025; power factor 0.8; fuel consumption for diesel with a density of 0.85 kg/L. Model availability and lead time are confirmed in the commercial offer.

Scope of supply and control

  • Set-mounted radiator with engine-driven fan, cooling system rated for +40 °C ambient
  • Anti-vibration mounts between engine, alternator and base frame
  • Base frame fuel tank (up to and including 825 kVA), oil and coolant drains with valves
  • Protective guards for fan and rotating parts
  • Exhaust bellows and industrial silencer
  • 12 or 24 V starter motor and battery
  • 3-pole output circuit breaker
  • Factory test of every set at 0, 25, 50, 75, 100 and 110 % load
  • Compliance with ISO 8528, ISO 3046, IEC 60034, BS 5000; manufacturing to ISO 9001 and ISO 14001; CE certificate

Control and protection

  • Standard controller with protections: high coolant temperature, low oil pressure, overspeed, start failure, over and under frequency and voltage, overload, overcurrent, emergency stop
  • Measurements: voltage, current, frequency, power factor, kW, kWh, kVA, running hours, number of starts
  • Options: automatic mains failure, fuel level, RS485 and Modbus RTU, Modbus TCP/IP, SNMP, extension modules
  • Alternative controllers: ComAp, DeepSea, Woodward, Smartgen
  • Parallel operation between sets and with the grid

Request

Tell us about your site

Load and load profile, operating mode (backup or primary source), climate, grid availability, noise and fuel requirements. We will reply with a configuration, lead time and proposal.

Add details: name, country, file

Prefer a messenger? Write to an engineer on Telegram or WhatsApp - we reply during business hours.

Request