Genset selector

Diesel genset LRYC825

825 kVA standby and 750 kVA prime, 50 Hz, 400/230 V. Yuchai YC6TD1000-D30 engine, Energis EG-800-4 alternator, ISO 8528 class G3.

Diesel genset LRYC825

All models / 50 Hz / LRYC825

Standby825 kVA660 kW
Prime750 kVA600 kW
Fuel at 100 %164 L/hStandby 185 L/h
Specific fuel0.273L/kWh
Canopy weight6,950 kg5,200 × 1,920 × 2,200
Enclosuresoundproof canopyISO 8528 G3 · 400/230 V

Ratings by voltage

Voltage, VStandby, kVAStandby, kWPrime, kVAPrime, kWCurrent, A
380/2208256607506001,253
400/2308256607506001,190
415/2408256607506001,147

Ratings per ISO 8528 at PF 0.8.

Fuel consumption

Datasheet values at 50, 75 and 100 % of prime and in standby duty.

0100200 0200400600 kW L/h 89127164185
LoadPower, kWFuel, L/hL/kWh
50 %300890.297
75 %4501270.282
100 %6001640.273
Standby6601850.28

Engine

Make
Yuchai
Model
YC6TD1000-D30
Cylinders
6 in line
Bore × stroke, mm
152 / 180
Aspiration
turbocharged and aftercooled
Compression ratio
14:1
Displacement, L
19.6
Speed, rpm
1,500
Governor
electronic
Engine prime power, kW
668
Engine maximum power, kW
735
Oil capacity, L
52
Starter, V
24

Alternator

Make
Energis
Model
EG-800-4
Protection
IP21
Insulation class
H
Efficiency at 100 %, PF 0.8, %
93.7
Excitation
auxiliary winding
Voltage regulator
KR440
Voltage regulation
± 1 %

Dimensions and weight

VersionLength, mmWidth, mmHeight, mmWeight, kgTank, L
Open on base frame3,8501,5002,0006,2001,200
Canopy (soundproof canopy)5,2001,9202,2006,9501,200

Specifications are manufacturer datasheet data, edition 08.2025; power factor 0.8; fuel consumption for diesel with a density of 0.85 kg/L. Model availability and lead time are confirmed in the commercial offer.

Scope of supply and control

  • Set-mounted radiator with engine-driven fan, cooling system rated for +40 °C ambient
  • Anti-vibration mounts between engine, alternator and base frame
  • Base frame fuel tank (up to and including 825 kVA), oil and coolant drains with valves
  • Protective guards for fan and rotating parts
  • Exhaust bellows and industrial silencer
  • 12 or 24 V starter motor and battery
  • 3-pole output circuit breaker
  • Factory test of every set at 0, 25, 50, 75, 100 and 110 % load
  • Compliance with ISO 8528, ISO 3046, IEC 60034, BS 5000; manufacturing to ISO 9001 and ISO 14001; CE certificate

Control and protection

  • Standard controller with protections: high coolant temperature, low oil pressure, overspeed, start failure, over and under frequency and voltage, overload, overcurrent, emergency stop
  • Measurements: voltage, current, frequency, power factor, kW, kWh, kVA, running hours, number of starts
  • Options: automatic mains failure, fuel level, RS485 and Modbus RTU, Modbus TCP/IP, SNMP, extension modules
  • Alternative controllers: ComAp, DeepSea, Woodward, Smartgen
  • Parallel operation between sets and with the grid

Request

Tell us about your site

Load and load profile, operating mode (backup or primary source), climate, grid availability, noise and fuel requirements. We will reply with a configuration, lead time and proposal.

Add details: name, country, file

Prefer a messenger? Write to an engineer on Telegram or WhatsApp - we reply during business hours.

Request