Genset selector

Diesel genset LRYC100X

100 kVA standby and 90 kVA prime, 60 Hz, 220/127 V. Yuchai YC6B130Z-D20 engine, Energis EG-75-4 alternator, ISO 8528 class G3.

Diesel genset LRYC100X

All models / 60 Hz / LRYC100X

Standby100 kVA80 kW
Prime90 kVA72 kW
Fuel at 100 %22.7 L/hStandby 26.6 L/h
Specific fuel0.315L/kWh
Canopy weight1,420 kg2,650 × 1,120 × 1,500
Enclosuresoundproof canopyISO 8528 G3 · 220/127 V

Ratings by voltage

Voltage, VStandby, kVAStandby, kWPrime, kVAPrime, kWCurrent, A
220/127100809072262
440/254100809072131
480/277100809072120

Ratings per ISO 8528 at PF 0.8.

Fuel consumption

Datasheet values at 50, 75 and 100 % of prime and in standby duty.

0102030 0255075 kW L/h 11.51722.726.6
LoadPower, kWFuel, L/hL/kWh
50 %3611.50.319
75 %54170.315
100 %7222.70.315
Standby8026.60.333

Engine

Make
Yuchai
Model
YC6B130Z-D20
Cylinders
6 in line
Bore × stroke, mm
108 / 125
Aspiration
turbocharged and aftercooled
Compression ratio
17.5:1
Displacement, L
6.87
Speed, rpm
1,800
Governor
electronic
Engine prime power, kW
88
Engine maximum power, kW
97
Oil capacity, L
17
Starter, V
24

Alternator

Make
Energis
Model
EG-75-4
Protection
IP21
Insulation class
H
Efficiency at 100 %, PF 0.8, %
89.6
Excitation
auxiliary winding
Voltage regulator
KRS440B
Voltage regulation
± 1 %

Dimensions and weight

VersionLength, mmWidth, mmHeight, mmWeight, kgTank, L
Open on base frame2,2001,0001,2751,100250
Canopy (soundproof canopy)2,6501,1201,5001,420250

Specifications are manufacturer datasheet data, edition 08.2025; power factor 0.8; fuel consumption for diesel with a density of 0.85 kg/L. Model availability and lead time are confirmed in the commercial offer.

Scope of supply and control

  • Set-mounted radiator with engine-driven fan, cooling system rated for +40 °C ambient
  • Anti-vibration mounts between engine, alternator and base frame
  • Base frame fuel tank (up to and including 825 kVA), oil and coolant drains with valves
  • Protective guards for fan and rotating parts
  • Exhaust bellows and industrial silencer
  • 12 or 24 V starter motor and battery
  • 3-pole output circuit breaker
  • Factory test of every set at 0, 25, 50, 75, 100 and 110 % load
  • Compliance with ISO 8528, ISO 3046, IEC 60034, BS 5000; manufacturing to ISO 9001 and ISO 14001; CE certificate

Control and protection

  • Standard controller with protections: high coolant temperature, low oil pressure, overspeed, start failure, over and under frequency and voltage, overload, overcurrent, emergency stop
  • Measurements: voltage, current, frequency, power factor, kW, kWh, kVA, running hours, number of starts
  • Options: automatic mains failure, fuel level, RS485 and Modbus RTU, Modbus TCP/IP, SNMP, extension modules
  • Alternative controllers: ComAp, DeepSea, Woodward, Smartgen
  • Parallel operation between sets and with the grid

Request

Tell us about your site

Load and load profile, operating mode (backup or primary source), climate, grid availability, noise and fuel requirements. We will reply with a configuration, lead time and proposal.

Add details: name, country, file

Prefer a messenger? Write to an engineer on Telegram or WhatsApp - we reply during business hours.

Request