Genset selector

Diesel genset LRYC125X

125 kVA standby and 110 kVA prime, 60 Hz, 220/127 V. Yuchai YC6B160Z-D20 engine, Energis EG-100-4 alternator, ISO 8528 class G3.

Diesel genset LRYC125X

All models / 60 Hz / LRYC125X

Standby125 kVA100 kW
Prime110 kVA88 kW
Fuel at 100 %28.2 L/hStandby 32 L/h
Specific fuel0.32L/kWh
Canopy weight1,570 kg2,650 × 1,120 × 1,500
Enclosuresoundproof canopyISO 8528 G3 · 220/127 V

Ratings by voltage

Voltage, VStandby, kVAStandby, kWPrime, kVAPrime, kWCurrent, A
220/12712510011088328
440/25412510011088164
480/27712510011088150

Ratings per ISO 8528 at PF 0.8.

Fuel consumption

Datasheet values at 50, 75 and 100 % of prime and in standby duty.

0102030 050100 kW L/h 142128.232
LoadPower, kWFuel, L/hL/kWh
50 %44140.318
75 %66210.318
100 %8828.20.32
Standby100320.32

Engine

Make
Yuchai
Model
YC6B160Z-D20
Cylinders
6 in line
Bore × stroke, mm
108 / 125
Aspiration
turbocharged and aftercooled
Compression ratio
17.5:1
Displacement, L
6.87
Speed, rpm
1,800
Governor
electronic
Engine prime power, kW
107
Engine maximum power, kW
118
Oil capacity, L
17
Starter, V
24

Alternator

Make
Energis
Model
EG-100-4
Protection
IP21
Insulation class
H
Efficiency at 100 %, PF 0.8, %
89.5
Excitation
auxiliary winding
Voltage regulator
KRS440B
Voltage regulation
± 1 %

Dimensions and weight

VersionLength, mmWidth, mmHeight, mmWeight, kgTank, L
Open on base frame2,2001,0001,2751,250250
Canopy (soundproof canopy)2,6501,1201,5001,570250

Specifications are manufacturer datasheet data, edition 08.2025; power factor 0.8; fuel consumption for diesel with a density of 0.85 kg/L. Model availability and lead time are confirmed in the commercial offer.

Scope of supply and control

  • Set-mounted radiator with engine-driven fan, cooling system rated for +40 °C ambient
  • Anti-vibration mounts between engine, alternator and base frame
  • Base frame fuel tank (up to and including 825 kVA), oil and coolant drains with valves
  • Protective guards for fan and rotating parts
  • Exhaust bellows and industrial silencer
  • 12 or 24 V starter motor and battery
  • 3-pole output circuit breaker
  • Factory test of every set at 0, 25, 50, 75, 100 and 110 % load
  • Compliance with ISO 8528, ISO 3046, IEC 60034, BS 5000; manufacturing to ISO 9001 and ISO 14001; CE certificate

Control and protection

  • Standard controller with protections: high coolant temperature, low oil pressure, overspeed, start failure, over and under frequency and voltage, overload, overcurrent, emergency stop
  • Measurements: voltage, current, frequency, power factor, kW, kWh, kVA, running hours, number of starts
  • Options: automatic mains failure, fuel level, RS485 and Modbus RTU, Modbus TCP/IP, SNMP, extension modules
  • Alternative controllers: ComAp, DeepSea, Woodward, Smartgen
  • Parallel operation between sets and with the grid

Request

Tell us about your site

Load and load profile, operating mode (backup or primary source), climate, grid availability, noise and fuel requirements. We will reply with a configuration, lead time and proposal.

Add details: name, country, file

Prefer a messenger? Write to an engineer on Telegram or WhatsApp - we reply during business hours.

Request