Genset selector

Diesel genset LRYC160

160 kVA standby and 145 kVA prime, 50 Hz, 400/230 V. Yuchai YC6B205L-D20 engine, Energis EG-150-4 alternator, ISO 8528 class G3.

Diesel genset LRYC160

All models / 50 Hz / LRYC160

Standby160 kVA128 kW
Prime145 kVA116 kW
Fuel at 100 %34 L/hStandby 38 L/h
Specific fuel0.293L/kWh
Canopy weight1,880 kg3,520 × 1,250 × 1,650
Enclosuresoundproof canopyISO 8528 G3 · 400/230 V

Ratings by voltage

Voltage, VStandby, kVAStandby, kWPrime, kVAPrime, kWCurrent, A
380/220160128145116243
400/230160128145116230
415/240160128145116222

Ratings per ISO 8528 at PF 0.8.

Fuel consumption

Datasheet values at 50, 75 and 100 % of prime and in standby duty.

02040 050100 kW L/h 17.825.53438
LoadPower, kWFuel, L/hL/kWh
50 %5817.80.307
75 %8725.50.293
100 %116340.293
Standby128380.297

Engine

Make
Yuchai
Model
YC6B205L-D20
Cylinders
6 in line
Bore × stroke, mm
108 / 125
Aspiration
turbocharged and aftercooled
Compression ratio
17.5:1
Displacement, L
6.87
Speed, rpm
1,500
Governor
electronic
Engine prime power, kW
138
Engine maximum power, kW
152
Oil capacity, L
20
Starter, V
24

Alternator

Make
Energis
Model
EG-150-4
Protection
IP21
Insulation class
H
Efficiency at 100 %, PF 0.8, %
91.6
Excitation
auxiliary winding
Voltage regulator
KRS440B
Voltage regulation
± 1 %

Dimensions and weight

VersionLength, mmWidth, mmHeight, mmWeight, kgTank, L
Open on base frame2,5501,0001,4501,500400
Canopy (soundproof canopy)3,5201,2501,6501,880400

Specifications are manufacturer datasheet data, edition 08.2025; power factor 0.8; fuel consumption for diesel with a density of 0.85 kg/L. Model availability and lead time are confirmed in the commercial offer.

Scope of supply and control

  • Set-mounted radiator with engine-driven fan, cooling system rated for +40 °C ambient
  • Anti-vibration mounts between engine, alternator and base frame
  • Base frame fuel tank (up to and including 825 kVA), oil and coolant drains with valves
  • Protective guards for fan and rotating parts
  • Exhaust bellows and industrial silencer
  • 12 or 24 V starter motor and battery
  • 3-pole output circuit breaker
  • Factory test of every set at 0, 25, 50, 75, 100 and 110 % load
  • Compliance with ISO 8528, ISO 3046, IEC 60034, BS 5000; manufacturing to ISO 9001 and ISO 14001; CE certificate

Control and protection

  • Standard controller with protections: high coolant temperature, low oil pressure, overspeed, start failure, over and under frequency and voltage, overload, overcurrent, emergency stop
  • Measurements: voltage, current, frequency, power factor, kW, kWh, kVA, running hours, number of starts
  • Options: automatic mains failure, fuel level, RS485 and Modbus RTU, Modbus TCP/IP, SNMP, extension modules
  • Alternative controllers: ComAp, DeepSea, Woodward, Smartgen
  • Parallel operation between sets and with the grid

Request

Tell us about your site

Load and load profile, operating mode (backup or primary source), climate, grid availability, noise and fuel requirements. We will reply with a configuration, lead time and proposal.