Genset selector

Diesel genset LRYC275

275 kVA standby and 250 kVA prime, 50 Hz, 400/230 V. Yuchai YC6MK350L-D20 engine, Energis EG-250-4 alternator, ISO 8528 class G2.

Diesel genset LRYC275

All models / 50 Hz / LRYC275

Standby275 kVA220 kW
Prime250 kVA200 kW
Fuel at 100 %56 L/hStandby 63 L/h
Specific fuel0.28L/kWh
Canopy weight2,550 kg3,900 × 1,500 × 1,800
Enclosuresoundproof canopyISO 8528 G2 · 400/230 V

Ratings by voltage

Voltage, VStandby, kVAStandby, kWPrime, kVAPrime, kWCurrent, A
380/220275220250200417
400/230275220250200396
415/240275220250200382

Ratings per ISO 8528 at PF 0.8.

Fuel consumption

Datasheet values at 50, 75 and 100 % of prime and in standby duty.

0204060 0100200 kW L/h 28425663
LoadPower, kWFuel, L/hL/kWh
50 %100280.28
75 %150420.28
100 %200560.28
Standby220630.286

Engine

Make
Yuchai
Model
YC6MK350L-D20
Cylinders
6 in line
Bore × stroke, mm
123 / 145
Aspiration
turbocharged and aftercooled
Compression ratio
16.8:1
Displacement, L
10.34
Speed, rpm
1,500
Governor
electronic
Engine prime power, kW
235
Engine maximum power, kW
259
Oil capacity, L
28
Starter, V
24

Alternator

Make
Energis
Model
EG-250-4
Protection
IP21
Insulation class
H
Efficiency at 100 %, PF 0.8, %
92.7
Excitation
auxiliary winding
Voltage regulator
Ks440
Voltage regulation
± 1 %

Dimensions and weight

VersionLength, mmWidth, mmHeight, mmWeight, kgTank, L
Open on base frame3,0001,1501,6502,100600
Canopy (soundproof canopy)3,9001,5001,8002,550600

Specifications are manufacturer datasheet data, edition 08.2025; power factor 0.8; fuel consumption for diesel with a density of 0.85 kg/L. Model availability and lead time are confirmed in the commercial offer.

Scope of supply and control

  • Set-mounted radiator with engine-driven fan, cooling system rated for +40 °C ambient
  • Anti-vibration mounts between engine, alternator and base frame
  • Base frame fuel tank (up to and including 825 kVA), oil and coolant drains with valves
  • Protective guards for fan and rotating parts
  • Exhaust bellows and industrial silencer
  • 12 or 24 V starter motor and battery
  • 3-pole output circuit breaker
  • Factory test of every set at 0, 25, 50, 75, 100 and 110 % load
  • Compliance with ISO 8528, ISO 3046, IEC 60034, BS 5000; manufacturing to ISO 9001 and ISO 14001; CE certificate

Control and protection

  • Standard controller with protections: high coolant temperature, low oil pressure, overspeed, start failure, over and under frequency and voltage, overload, overcurrent, emergency stop
  • Measurements: voltage, current, frequency, power factor, kW, kWh, kVA, running hours, number of starts
  • Options: automatic mains failure, fuel level, RS485 and Modbus RTU, Modbus TCP/IP, SNMP, extension modules
  • Alternative controllers: ComAp, DeepSea, Woodward, Smartgen
  • Parallel operation between sets and with the grid

Request

Tell us about your site

Load and load profile, operating mode (backup or primary source), climate, grid availability, noise and fuel requirements. We will reply with a configuration, lead time and proposal.

Add details: name, country, file

Prefer a messenger? Write to an engineer on Telegram or WhatsApp - we reply during business hours.

Request