Integrated cabinet - versions

Integrated cabinet versions

From a cabinet inside a building to a multi-operator row and a pole-mounted module. Full specifications, no registration or request needed.

Cabinets and module

Weights exclude rectifier modules and batteries.

Indoor integrated cabinet

Indoor cabinet

Replaces a shelter inside a building

W×D×H
600 × 600 × 2,000 mm
Weight
under 120 kg
Cooling
natural
Cable entry
top
Service access
front
Protection
IP20, class B1 indoor rooms
Catalog card
All-weather integrated cabinet

All-weather cabinet

Street, rooftop, pole site; single operator

W×D×H
750 × 750 × 2,100 mm, 200 mm plinth
Weight
under 210 kg
Cooling
1.5 kW DC air conditioner, up to 2 units, shared by equipment and battery compartments
Cable entry
bottom or between cabinets
Service access
front and rear
Noise
max 65 dB at 1.5 m, +45 °C
Protection
IP55, sandwich panels
Catalog card
Multi-service cabinet

Multi-service cabinet

Several operators, tower companies, sites up to 36 kW

W×D×H
900 × 1,200 × 2,100 mm, 200 mm plinth
Weight
under 430 kg
Row
up to 4 cabinets with inter-cabinet cabling and shared cooling
Cooling
2 × 5 kW DC air conditioners, up to 4 with N+1, up to 10 kW per cabinet
Equipment space
31U up to 790 mm deep or 2 × 31U up to 396 mm deep, 19 and 21-inch
Batteries
up to 12 modules of 100 Ah in 3U
Power system
36 kW in a 6U shelf, 9 module slots
Protection
IP55, foamed enclosure
Catalog card

Pole-mounted power module

Micro and small sites with no ground space

Power module
6 kW, 120 × 300 × 420 mm, about 18 kg
Battery module
3 kW, 50 Ah, about 26 kg
Mounting
wall, pole or tower; two people in 30 minutes
Parallel
up to 4 power modules and up to 8 battery modules
Protection
IP65, natural cooling
Temperature
-40 to +55 °C without solar radiation
Load
7 branches of 40 A with per-branch metering and shedding
System efficiency
97 %

Power system: 24-36 kW in 6U

The multi-input power system accepts grid, generator and solar and delivers voltages for different operators’ equipment.

Capacity
24 kW in 6U, up to 36 kW with three-phase input
Input
three-phase 85-300 V AC, 45-65 Hz, 100 A breaker, optional dual input with interlock
DC output
42-58 V, rated 53.5 V; 57 V mode for long radio feed lines
Outputs
12, 24, 36, 48, 57 V DC; 24, 220 V AC
Battery branches
6 × 125 A
Load groups
primary 4 × 125 A; secondary 2 × 63 A, 2 × 32 A, 2 × 16 A
Surge protection
AC 30 kA; DC 10 kA differential, 20 kA common mode
Rectifier efficiency
up to 98 % peak
Service
front access, 19-inch rack mount, under 30 kg without modules

Cooling for indoor cabinets

For shelters that stay: the cooling unit is built into the door or mounted on the side of the cabinet.

VersionCabinet W×D×H, mmCompressor coolingHeat pipe coolingEfficiency
Door unit, inverter compressor600 × 600 × 2,000 / 600 × 800 × 2,2005.5+ / 11+ kW-EER 3.4
Door unit, compressor and heat pipe600 × 600 × 2,000 / 600 × 800 × 2,2006+ / 10+ kW4+ / 6+ kWEER 3+, heat pipe 10+
Side unit, compressor and heat pipe600 × 600 × 2,000 / 600 × 800 × 2,2006+ / 10+ kW4+ / 6+ kWEER 3+, heat pipe 10+

48 V modules for a 19-inch rack: sodium NFPP for frost and daily cycling, lithium LFP for climate-controlled sites.

Cabinet, power system and cooling specifications are manufacturer data; confirmed in the site-specific specification.

Request

Tell us about your sites

Number of sites, type (rooftop, ground, pole), climate, equipment load, how many operators share the site and what is installed today. We will reply with a cabinet configuration and pilot terms.

Add details: name, country, file

Prefer a messenger? Write to an engineer on Telegram or WhatsApp - we reply during business hours.

Request